500,000 hour MTBF
Safety rated for Medical, Industrial, IT and other applications
Wide operating input voltage range: 80 Vac to 275 Vac or 120 Vdc to 300 Vdc
Wide adjustable output voltage range
Low profile 1U design
Variable speed fan with low acoustic noise level of less than 38.5 dB(A)
High efficiency: up to 94%
Redundant operation with active current sharing
High isolation: 2 × MOPP
PMBus™ compatible for control, programming and monitoring
3 years warranty
Dimensions (L x W x D) : | 203.1 x 101.6 x 40.6 mm |
8.00" x 4.00" x 1.60" |
Unit Weight : | 1.1 kg (2.43 lb) |
Nominal Output Voltage 48V |
Output Voltage Adjustment Range 38.4-56.0V |
Output Current 12.5A |
Output Power 600W |
Start-up Time < 2.5 s (@ AC OFF to ON, max. load) < 150 ms (@ REMOTE OFF to ON, max. load) |
Hold-up Time 20 msec nominal |
Dynamic Response (Overshoot & Undershoot O/P Voltage) < 5% |
Nominal Input Voltage 100-240Vac |
Input Voltage Range 80-275Vac (120-300Vdc) |
Nominal Input Frequency 50-60Hz |
Input Frequency Range 47-63Hz |
Input Current 9A @ 80Vac 5.7A @ 120Vdc |
Efficiency at 100% load 92% @ 115Vac 94% @ 230Vac |
Max Inrush Current < 20A |
Power Factor at 100% load 0.9 (typical) |
Dimensions 203.1 x 101.6 x 40.6 mm 8.00" x 4.00" x 1.60" |
Unit Weight 1.1 kg (2.43 lb) |
Cooling System Fan with variable speed control |
Input Terminal Block M3.5 x 3 pins |
Output Terminal Block M4 x 2 pins |
Surrounding Air Temperature operating -20°C to +70°C |
Surrounding Air Temperature storage -40°C to +85°C |
Power De-rating When AC input voltage is < 90 Vac, the output power will be reduced by 6 W per 1 V. |
Operating Humidity < 95% (non-condensing) |
Shock Test (Non-Operating) IEC 60068-2-27 compliant, 50 g, 11 msec, 3 shocks for each direction |
Vibration Test (Non-Operating) IEC 60068-2-6 compliant, 2.09 Grms, 5 Hz to 500 Hz, 20 minutes per side (3 planes) |
Overvoltage YES, latch mode 58.5V to 63V |
Overload / Overcurrent YES, at 108% to 140% of nominal output current; auto recovery |
Over Temperature YES, auto recovery |
Short Circuit YES, auto recovery |
500,000 hours (Telecordia SR-332, Issue 3, 25 °C, 90% confidence level)
Medical Safety IEC 60601-1(2005), EN60601-1(2006) ANSI/AAMI ES 60601-1(2005) CAN/CSA C22.2 No. 60601-1 (2008); 3,000 m (9,800 ft) altitude, 100 V to 240 Vac ±10% (UL File E325662) |
Galvanic Isolation UL 60950-1/CSA 22.2 No 60950-1, Edition 2; 5,000 m (16,400 ft) altitude, 120 V to 300 Vdc and 100 V to 240 ±10% Vac (UL File E191395) |
Emission EN 55011, EN 55022 and FCC, Class B |
Harmonic Current Emissions EN 61000-3-2, Class A |