DRC系列导轨式24V直流电源供应器DRC-24V10W1AZ
Highlights & Features
Protection Class II, Double Isolation (No Earth connection is required)
Universal AC input voltage and full power up to 55°C
Power will not de-rate for the entire input voltage range
Efficiency > 80.0% @ 115Vac & 230Vac
NEC Class 2 / Limited Power Source (LPS) certified
Overvoltage / Overcurrent / Over Temperature Protections
Dimensions (L x W x D): 91 x 18 x 55.6 mm
Unit Weight: 0.065 kg
Nominal Output Voltage24V
Output Current0.42A
Output Power10W
Line Regulation< 1% typ. (@ 90-264Vac, 100% load)
Load Regulation< 2% typ. (@ 90-264Vac, 100% load)
PARD(20MHz)< 50mVpp
Start-up Time< 3,000ms @ nominal input (100% load)
Hold-up Time> 10ms @ 115Vac,
> 30ms @ 230Vac (100% load)
Dynamic Response± 5% @ 10-100% load
Start-up with Capacitive Loads3,000µF Max
Input Voltage Range90-264 Vac (125-375 Vdc)
Max Input Voltage100-240Vac
Nominal Input Frequency50-60Hz
Input Frequency Range47-63Hz
Nominal DC Input Voltage125-375Vdc
Input Current< 0.30A @ 115Vac,
< 0.20A @ 230Vac
Efficiency at 100% load> 80.0% @ 115Vac & 230Vac
Max. Inrush Current< 15A @ 115Vac,
< 30A @ 230Vac
Leakage Current< 0.25mA @ 240Vac
Case Chassis / Case CoverPlastic
Dimensions (L x W x D)91 x 18 x 55.6 mm
Unit Weight0.065 kg
IndicatorGreen LED (DC OK)
Cooling SystemConvection
Input TerminalM4 x 2 Pins (Rated 300V/16A)
Output TerminalM4 x 2 Pins (Rated 300V/16A)
ENVIRONMENT / PROTECTIONS / RELIABILITY / SAFETY / EMC
Operating Ambient Temperature-25°C to +71°C
Storage Ambient Temperature-25°C to +85°C
Power De-rating> 55°C de-rate power by 2.5% /°C
Operating Humidity5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 shocks for each 3 directions, 9 times in total
Vibration Test (Non-Operating)IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions
Overvoltage Protection< 34.8V, SELV Output, Latch-off Mode
Overload / Overcurrent Protection> 120% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Over Temperature Protection> 75°C Surrounding Air Temperature @ 100% load, Latch-off Mode
Short Circuit ProtectionHicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionIP20
Protection Against ShockClass II (No Primary Earth connection is required)
MTBF> 500,000 hrs. as per Telcordia SR-332
Galvanic IsolationInput to Output: 3.0KVac
EmissionsCISPR22, EN55022, FCC Title 47: Class B
ImmunityEN55024
Electrical SafetyUL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E338991)
ITETUV Bauart to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E131881),
CB scheme to IEC 60950-1, Limited Power Source (LPS)
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC