DRC系列导轨式24V直流电源供应器DRC-24V60W1AZ
Highlights & Features
Protection Class II, Double Isolation
(No Earth connection is required)
Universal AC input voltage and full power up to 55°C
Power will not de-rate for the entire input voltage range
Efficiency > 88.0% @ 115Vac & 230Vac
NEC Class 2 / Limited Power Source (LPS) certified
Overvoltage / Overcurrent / Over Temperature Protections
Nominal Output Voltage24V
Output Voltage Adjustment Range24-28Vdc
Output Current2.5A
Output Power60W
Line Regulation< 1% typ. (@ 90-264Vac, 100% load)
Load Regulation< 2% typ. (@ 90-264Vac, 100% load)
PARD(20MHz)150mVpp
Start-up Time< 3,000ms @ nominal input (100% load)
Hold-up Time> 16ms @ 115Vac,
> 30ms @ 230Vac (100% load)
Dynamic Response± 5% @ 10-100% load
Start-up with Capacitive Loads3,000μF Max
Nominal Input Voltage100-240Vac
Input Voltage Range90-264 Vac (125-375Vdc)
Input Frequency Range47-63Hz
Input Current< 1.50A@115Vac,
< 1.00A @ 230Vac
Max. Inrush Current< 30A @ 115Vac,
< 60A @ 230Vac
Power FactorConform to EN 61000-3-2
Leakage Current< 0.25mA @ 240Vac
Case Chassis / Case CoverPlastic
Dimensions (L x W x D)91 x 71 x 55.6 mm
Unit Weight0.24 kg
IndicatorGreen LED (DC OK)
Input Terminal2 Pins (Rated 300V/25A)
Output Terminal4 Pins (Rated 300V/25A)
Noise Sound Pressure Level (SPL)< 25dBA
Mounting RailStandard TS35 DIN Rail in accordance with EN 60715
WireAWG 22-12
Operating Ambient Temperature-25°C to +71°C
Storage Ambient Temperature-25°C to +85°C
Power De-rating> 55°C de-rate power by 2.5% / °C
Operating Humidity5 to 95% RH (Non-Condensing)
Overvoltage Protection< 34.8V, SELV Output, Latch-off Mode
Overload / Overcurrent Protection> 110% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Over Temperature Protection< 75°C Surrounding Air Temperature @ 100% load, Latch-off Mode
Short Circuit ProtectionHiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of ProtectionClass II (No Primary Earth connection is required)
MTBF> 500,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
Galvanic Isolation3.0KVac
EmissionsCISPR 22, EN 55022, FCC Title 47: Class A
Electrical SafetyUL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File no. E338991)
ITETUV to EN 60950-1,
UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File no. E131881),
CB scheme to IEC 60950-1, Limited Power Source (LPS)
CEIn conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC